Application For use on 3 phase protective multiple earthed (PME) electrical services. These cables are designed for use in buildings due to their fire performance characteristics. . Fire performance - Low smoke: BS EN 50268 1 & 2.
- Halogen free: BS EN 50267-2-1.
- Low toxicity: BS EN 50267-2-1.
Design 1. Conductor - Class 1 sector shaped solid aluminium in accordance with BS6360 and IEC 60228.
2. Insulation - XLPE compound type GP8 to EN60811 / BS7655-1.3
3. Bedding - Synthetic bedding tape, approx. 0.5mm thick
4. Concentric combined neutral/earth conductor - Annealed copper wires applied helically around phase conductor.
5. Sheath - Orange LSHF compound type LTS 1 to BS 7655-6.1 or EN 60811
Marking - All cables(White Print): 0000M Batch No 0000
- All cables(Embossed): )( ELECTRIC CABLE 600/1000V BS7870-3.50 3 x size, year
Core Identification - Three cores: Brown - Black - Grey
|