LINEAX® - H07RNF

Send link to this page PDF Your Nexans contact on this page
LINEAX® - H07RNF Secondary circuit cable 450/750 V
Standards
International  HD 22.4
National  NF C 32-102-4
Description

Applications

Connection between transformers and Airfield Lighting Equipment. This cable can be buried providing there is an extra mechanicalprotection.

Design

  1. Conductor
    Flexible bare copper, Class 5
  2. Insulation
    Special cross linked elastomer
  3. Outer sheath
    Cross linked Oil resistant elastomer
    Colour: black

Core Identification

2 cores: brown + blue, 3 cores: brown + blue + Green/Yellow


 TOP
Characteristics
Construction characteristics
Conductor material Bare copper  
Conductor flexibility Flexible class 5  
Insulation Special cross-linked elastomer  
Outer sheath Cross-linked elastomer  
Sheath colour Black  
Electrical characteristics
Rated Voltage Uo/U (Um) 450 / 750 V  
Mechanical characteristics
Mechanical resistance to impacts Good  
Cable flexibility Flexible  
Usage characteristics
Field of application Secondary Circuit  
Weather resistance Very good  
Chemical resistance Accidental  
Water proof Temporary  
Ambient installation temperature, range -20 .. 85°C  
Max. conductor temperature in service 85°C  
Packaging Cut to length  

 TOP
Your selection
Conductor cross-section  mm²
Permissible current (one phase)  A
Number of cores  
Voltage drop, single phase  V/A.km
Minimum outer diameter  mm
Maximum outer diameter  mm
Approximate weight  kg/km
Apply
Reset
Results   9/9
Select all Items Nexans ref. Name Conductor cross-section (mm²) Permissible current (one phase) (A) Number of cores Voltage drop, single phase (V/A.km)
22.1 1 x 2.5 2.5 32.0 1 14.0
22.2 1 x 4 4 43.0 1 8.7
22.3 1 x 6 6 56.0 1 5.9
22.4 2 x 2.5 2.5 32.0 2 16.2
22.5 2 x 4 4 43.0 2 10.1
22.6 2 x 6 6 56.0 2 6.7
22.7 3 x 2,5 2.5 32.0 3 16.2
22.8 3 x 4 4 43.0 3 10.1
22.9 3 x 6 6 56.0 3 7.0
Add to favorites

 TOP
Characteristics

Permissible current ratings are shown for an ambient temperature at 30°C where the cable is installed in fixed installations for a maximum operating and 
a conductor temperature of 85°C

 

Bending radius

 

 

For movable installations: 

6 to 8 x Outer diameter

 

 

For fixed installations:

3 x Outer diameter if ≤ 12mm

 

 

 

4 x Outer diameter if > 12

 

 