H05G-K

Send link to this page PDF Your Nexans contact on this page
H05G-K Cable with increased heat resistance for internal wiring
Standards
International  HD 22.7
National  DIN VDE 0282 part 1; DIN VDE 0282 part 7; DIN VDE 0293; DIN VDE 0295
Description

Applications:

For internal wiring in dry locations only. For fxed installations elsewhere e.g. visible or embedded conduits or tubes.

 

Type Approval Certificates:

DIN VDE 0282 part  7

HD 22.7


 TOP
Characteristics
Construction characteristics
Conductor material Tinned copper  
Conductor flexibility Flexible class 5  
Insulation Rubber  
Halogen free Yes  
Dimensional characteristics
Average insulation thickness 0.6mm  
Electrical characteristics
Rated Voltage Uo/U 300 / 500 V  
Mechanical characteristics
Cable flexibility Flexible  
Mechanical resistance to impacts Good  
Usage characteristics
Operating temperature, range -25 .. 110°C  
Max. conductor temperature in service 110°C  

 TOP
Your selection
Conductor diameter  mm
Conductor cross-section  mm²
Nominal outer diameter  mm
Approximate weight  kg/km
Copper content  kg/km
Apply
Reset
Results   3/3
Select all Items Nexans ref. Name Conductor diameter (mm) Conductor cross-section (mm²) Nominal outer diameter (mm) Approximate weight (kg/km)
H05G-K 1 x 0,5 mm² 0.9 0.5 2.2 8
H05G-K 1 x 0,75 mm² 1.1 0.75 2.3 11
H05G-K 1 x 1 mm² 1.3 1 2.5 13
Add to favorites

 TOP
Marking : XNEXANSX < VDE > < HAR > H05G-K

 TOP