Characteristics
|
|
Conductor material
|
Copper
|
|
|
Conductor shape
|
Circular stranded (RM)
|
|
|
Material of the inner semi-conductor
|
XLPE
|
|
|
Insulation
|
XLPE (chemical)
|
|
|
Material of the external semi-conductor
|
XLPE
|
|
|
Screen
|
Copper tape
|
|
|
Protection
|
Filler
|
|
|
Armour type
|
Galvanized steel wires
|
|
|
Outer sheath
|
PVC
|
|
|
Number of cores
|
3
|
|
|
Conductor cross-section
|
150mm²
|
|
|
Screen section
|
25mm²
|
|
|
Nominal outer diameter
|
71.0mm
|
|
|
Approximate weight
|
10800kg/km
|
|
|
Delivery reel size for 1000m
|
250cm
|
|
|
Rated Voltage Uo/U
|
6.35 / 11 kV
|
|
|
Max. DC-resistance of the conductor at 20° C
|
0.124Ohm/km
|
|
|
Nominal inductance
|
0.3mH/km
|
|
|
Permissible current rating when buried
|
392A
|
|
|
Permissible current rating in open air
|
410A
|
|
|
Nominal phase capacitance
|
0.35µF / km
|
|
|
Mechanical resistance to impacts
|
Good
|
|
|
Packaging
|
Reel
|
|
|
Length
|
500m
|
|
|
Operating temperature, range
|
-20 .. 60°C
|
|
|
Maximum operating temperature
|
90°C
|
|
|
Short-circuit max. conductor temperature
|
250°C
|
|
|
Flame retardant
|
IEC 60332-1&3
|
|
|
Bending factor when laying
|
15(xD)
|
|