2XS(FL)2YRAA RM 06/10 (12) kV

Description
3 core XLPE-insulated cables with PE sheath and armouring, longitudinally and radially watertight
Description
Standards
International : IEC 60502-2Description
Stranded copper conductor class 2 according to IEC 60228, semi conducting conductor screen, insulation of cross-linked polyethylene (XLPE), semi conducting insulation screen, semi conducting bedding, copper screen with swellable powder, aluminium tape bonded to PE sheath, 3 core layed up, polypropylene yarn bedding, armouring of galvanized steel, hessian tape and polypropylene yarn serving.
Application in water, for example internal and external cabling of offshore windparks, power supply of islands, lighthouses and offshore plattforms.
Optionally watertight conductor with sealing compound, lead sheath and Fiber Optics or Control Cables in the interstices available. Other voltages and EPR insulated cables on request.
All medium voltage submarine cables are manufactured on the basis of specifications and can be adapted to the requirements of the customer. Therefore, all technical information are purely for information purposes and the electrical characteristics are calculated for water saturated seabeds and values which are specified in the data sheets. For your specific requirements and laying depths please don't hesitate to contact us.
Characteristics
Construction characteristics | |
---|---|
Number of conductors | 3 |
Type of conductor | Circular compacted stranded |
Insulating material | XLPE |
Screen | Copper wire |
Inner sheath | HDPE |
Armour type | Galvanised round steel wires |
Material used for longitudinal water tightness | Swelling powder |
Lead free | Yes |
Halogen free | Yes |
Dimensional characteristics | |
Nominal insulation thickness | 3.4mm |
Nominal outer sheath thickness | 2.5mm |
Electrical characteristics | |
Operating voltage | 10kV |
Maximum operating voltage | 12kV |
Grounding type | Solid bonding |
Load factor | 1 |
Thermal soil resistivity wet zone | 1K*m/W |
Usage characteristics | |
Number of systems | 1 |
Laying depth, center of system | 1000mm |
Ambient ground temperature | 20°C |
Bending factor when installed | 15(xD) |
Bending factor when laying | 30(xD) |
Longitudinal water tightness | Yes |
Water proof | Radial |
Mechanical Resistance | Good mechanical resistance |
Specific characteristics | |
See all products | |
|