CU/XLPE/SWA/LSZH BS 6724 5x16 mm²

GTIN 8680969020251

Dca-s2,d2,a2
See all ALSECURE® CU/XLPE/SWA/LSZH BS 6724 Dca Class products
Description
Standards
International : IEC 60502National : BS 6724
Declaration of Performance : Reaction to fire: Dca-s2,d2,a2
according to EN50575:2014+A1:2016
Description
Application:
Used in energy networks in hotels, schools, tunnels, high constructions,hospitals, power plants, data processing centers, business centers where there is a risk of fire
Construction:
- Conductor:Copper
- Insulation:XLPE
- Filler:EVA/PE based LSZH
- Wire armour : Single layer galvanized steel wire
- Outer sheath: LSZH (Low Smoke Zero Halogen)
Marking:
ELECTRIC CABLE 600/1000 V BS 6724 H NEXANS i
Nb. of cores x cross section "YEAR" BASEC ALSECURE
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Insulation | XLPE (Cross-linked Polyethylene) |
Material of filler / inner sheath | Halogen free filling compound |
Armour type | Galvanised round steel wires |
Outer sheath | LSZH |
Halogen free | IEC 60754-1 |
Sheath colour | Black |
Core identification | Numbers |
Conductor shape | Circular stranded (RM) |
Dimensional characteristics | |
Number of cores | 5 |
Conductor cross-section | 16mm² |
Nominal outer diameter | 25.0mm |
Approximate weight | 1600kg/km |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/1 kV |
Max. DC resistance of the conductor at 20°C | 1.15Ohm/km |
Permissible current rating in open air | 100A |
Permissible current rating when buried | 84A |
Usage characteristics | |
Operating temperature, range | -20 .. 60°C |
Short-circuit max. conductor temperature | 250°C |
Bending factor when laying | 8(xD) |
Smoke density | IEC 61034 |
Gases corrosivity | IEC 60754-2 |
Flame retardant | IEC 60332-3 Cat. C |
Max. conductor temperature in service | 90°C |