NX600 Armoured

Products

NX600 3x10 mm2

Nexans ref. 10539718 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Circular stranded (RM)
  • Core identification: Brown, black, grey
  • Inner sheath: None
  • Number of cores: 3
  • Approximate weight: 1110 kg/km
  • Conductor cross-section: 10 mm²
  • Nominal outer diameter: 24.0 mm
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
  • Permissible current rating clipped direct: 73 A
  • Permissible current rating in open air: 78 A
  • Permissible current rating when buried: 58 A
  • Permissible short circuit current conductor 1s: 1.4 kA
  • Voltage Drop: 4.0 V/A.km

 

NX600 3x120 mm2

Nexans ref. 10544560 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Core identification: Brown, black, grey
  • Inner sheath: LSZH
  • Number of cores: 3
  • Approximate weight: 5180 kg/km
  • Conductor cross-section: 120 mm²
  • Nominal outer diameter: 42.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Permissible current rating clipped direct: 335 A
  • Permissible current rating in open air: 353 A
  • Permissible current rating when buried: 223 A
  • Permissible short circuit current conductor 1s: 17.2 kA
  • Voltage Drop: 0.37 V/A.km

 

NX600 3x150 mm2

Nexans ref. 10544561 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Core identification: Brown, black, grey
  • Inner sheath: LSZH
  • Number of cores: 3
  • Approximate weight: 6530 kg/km
  • Conductor cross-section: 150 mm²
  • Nominal outer diameter: 47.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Permissible current rating clipped direct: 386 A
  • Permissible current rating in open air: 406 A
  • Permissible current rating when buried: 251 A
  • Permissible short circuit current conductor 1s: 21.4 kA
  • Voltage Drop: 0.3 V/A.km

 

NX600 3x16 mm2

Nexans ref. 10539719 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Circular stranded (RM)
  • Core identification: Brown, black, grey
  • Inner sheath: None
  • Number of cores: 3
  • Approximate weight: 1340 kg/km
  • Conductor cross-section: 16 mm²
  • Nominal outer diameter: 26.0 mm
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating clipped direct: 94 A
  • Permissible current rating in open air: 99 A
  • Permissible current rating when buried: 75 A
  • Permissible short circuit current conductor 1s: 2.3 kA
  • Voltage Drop: 2.5 V/A.km

 

NX600 3x185 mm2

Nexans ref. 10544562 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Core identification: Brown, black, grey
  • Inner sheath: LSZH
  • Number of cores: 3
  • Approximate weight: 7880 kg/km
  • Conductor cross-section: 185 mm²
  • Nominal outer diameter: 51.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.099 Ohm/km
  • Permissible current rating clipped direct: 441 A
  • Permissible current rating in open air: 463 A
  • Permissible current rating when buried: 281 A
  • Permissible short circuit current conductor 1s: 26.5 kA
  • Voltage Drop: 0.26 V/A.km

 

NX600 3x240 mm2

Nexans ref. 10544563 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Core identification: Brown, black, grey
  • Inner sheath: LSZH
  • Number of cores: 3
  • Approximate weight: 9880 kg/km
  • Conductor cross-section: 240 mm²
  • Nominal outer diameter: 57.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.075 Ohm/km
  • Permissible current rating clipped direct: 520 A
  • Permissible current rating in open air: 546 A
  • Permissible current rating when buried: 324 A
  • Permissible short circuit current conductor 1s: 34.3 kA
  • Voltage Drop: 0.21 V/A.km

 

NX600 3x25 mm2

Nexans ref. 10544555 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Circular stranded (RM)
  • Core identification: Brown, black, grey
  • Inner sheath: None
  • Number of cores: 3
  • Approximate weight: 1910 kg/km
  • Conductor cross-section: 25 mm²
  • Nominal outer diameter: 29.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Permissible current rating clipped direct: 124 A
  • Permissible current rating in open air: 131 A
  • Permissible current rating when buried: 96 A
  • Permissible short circuit current conductor 1s: 3.6 kA
  • Voltage Drop: 1.65 V/A.km

 

NX600 3x300 mm2

Nexans ref. 10544564 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Core identification: Brown, black, grey
  • Inner sheath: LSZH
  • Number of cores: 3
  • Approximate weight: 11810 kg/km
  • Conductor cross-section: 300 mm²
  • Nominal outer diameter: 62.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.06 Ohm/km
  • Permissible current rating clipped direct: 599 A
  • Permissible current rating in open air: 628 A
  • Permissible current rating when buried: 365 A
  • Permissible short circuit current conductor 1s: 42.9 kA
  • Voltage Drop: 0.18 V/A.km

 

NX600 3x35 mm2

Nexans ref. 10544556 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Circular stranded (RM)
  • Core identification: Brown, black, grey
  • Inner sheath: None
  • Number of cores: 3
  • Approximate weight: 2310 kg/km
  • Conductor cross-section: 35 mm²
  • Nominal outer diameter: 31.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Permissible current rating clipped direct: 154 A
  • Permissible current rating in open air: 162 A
  • Permissible current rating when buried: 115 A
  • Permissible short circuit current conductor 1s: 5 kA
  • Voltage Drop: 1.15 V/A.km

 

NX600 3x4 mm2

Nexans ref. 10539716 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Circular stranded (RM)
  • Core identification: Brown, black, grey
  • Inner sheath: None
  • Number of cores: 3
  • Approximate weight: 790 kg/km
  • Conductor cross-section: 4 mm²
  • Nominal outer diameter: 21.0 mm
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Permissible current rating clipped direct: 42 A
  • Permissible current rating in open air: 44 A
  • Permissible current rating when buried: 36 A
  • Permissible short circuit current conductor 1s: 0.6 kA
  • Voltage Drop: 10.0 V/A.km

 

NX600 3x400 mm2

Nexans ref. 10544565 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Core identification: Brown, black, grey
  • Inner sheath: LSZH
  • Number of cores: 3
  • Approximate weight: 14770 kg/km
  • Conductor cross-section: 400 mm²
  • Nominal outer diameter: 69.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
  • Permissible current rating clipped direct: 673 A
  • Permissible current rating in open air: 728 A
  • Permissible current rating when buried: - A
  • Permissible short circuit current conductor 1s: 57.2 kA
  • Voltage Drop: 0.17 V/A.km

 

NX600 3x50 mm2

Nexans ref. 10544557 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Core identification: Brown, black, grey
  • Inner sheath: LSZH
  • Number of cores: 3
  • Approximate weight: 2400 kg/km
  • Conductor cross-section: 50 mm²
  • Nominal outer diameter: 30.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Permissible current rating clipped direct: 187 A
  • Permissible current rating in open air: 197 A
  • Permissible current rating when buried: 135 A
  • Permissible short circuit current conductor 1s: 7.2 kA
  • Voltage Drop: 0.87 V/A.km

 

NX600 3x6 mm2

Nexans ref. 10539717 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Circular stranded (RM)
  • Core identification: Brown, black, grey
  • Inner sheath: None
  • Number of cores: 3
  • Approximate weight: 900 kg/km
  • Conductor cross-section: 6 mm²
  • Nominal outer diameter: 22.0 mm
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating clipped direct: 53 A
  • Permissible current rating in open air: 56 A
  • Permissible current rating when buried: 44 A
  • Permissible short circuit current conductor 1s: 0.9 kA
  • Voltage Drop: 6.8 V/A.km

 

NX600 3x70 mm2

Nexans ref. 10544558 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Core identification: Brown, black, grey
  • Inner sheath: LSZH
  • Number of cores: 3
  • Approximate weight: 3150 kg/km
  • Conductor cross-section: 70 mm²
  • Nominal outer diameter: 34.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Permissible current rating clipped direct: 238 A
  • Permissible current rating in open air: 251 A
  • Permissible current rating when buried: 167 A
  • Permissible short circuit current conductor 1s: 10 kA
  • Voltage Drop: 0.6 V/A.km

 

NX600 3x95 mm2

Nexans ref. 10544559 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Core identification: Brown, black, grey
  • Inner sheath: LSZH
  • Number of cores: 3
  • Approximate weight: 4270 kg/km
  • Conductor cross-section: 95 mm²
  • Nominal outer diameter: 39.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Permissible current rating clipped direct: 289 A
  • Permissible current rating in open air: 304 A
  • Permissible current rating when buried: 197 A
  • Permissible short circuit current conductor 1s: 13.6 kA
  • Voltage Drop: 0.45 V/A.km

 

NX600 4x16 mm2

Nexans ref. 10539733 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Circular stranded (RM)
  • Core identification: Blue, brown, black, grey
  • Inner sheath: None
  • Number of cores: 4
  • Approximate weight: 1600 kg/km
  • Conductor cross-section: 16 mm²
  • Nominal outer diameter: 28.0 mm
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating clipped direct: 94 A
  • Permissible current rating in open air: 99 A
  • Permissible current rating when buried: 75 A
  • Permissible short circuit current conductor 1s: 2.3 kA
  • Voltage Drop: 2.5 V/A.km

 

NX600 4x4 mm2

Nexans ref. 10539730 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Circular stranded (RM)
  • Core identification: Blue, brown, black, grey
  • Inner sheath: None
  • Number of cores: 4
  • Approximate weight: 910 kg/km
  • Conductor cross-section: 4 mm²
  • Nominal outer diameter: 22.0 mm
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Permissible current rating clipped direct: 42 A
  • Permissible current rating in open air: 44 A
  • Permissible current rating when buried: 36 A
  • Permissible short circuit current conductor 1s: 0.6 kA
  • Voltage Drop: 10.0 V/A.km

 

NX600 4x50 mm2

Nexans ref. 10539736 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Core identification: Blue, brown, black, grey
  • Inner sheath: LSZH
  • Number of cores: 4
  • Approximate weight: 3020 kg/km
  • Conductor cross-section: 50 mm²
  • Nominal outer diameter: 34.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Permissible current rating clipped direct: 187 A
  • Permissible current rating in open air: 197 A
  • Permissible current rating when buried: 135 A
  • Permissible short circuit current conductor 1s: 7.2 kA
  • Voltage Drop: 0.87 V/A.km

 

NX600 4x6 mm2

Nexans ref. 10539731 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor shape: Circular stranded (RM)
  • Core identification: Blue, brown, black, grey
  • Inner sheath: None
  • Number of cores: 4
  • Approximate weight: 1060 kg/km
  • Conductor cross-section: 6 mm²
  • Nominal outer diameter: 24.0 mm
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating clipped direct: 53 A
  • Permissible current rating in open air: 56 A
  • Permissible current rating when buried: 44 A
  • Permissible short circuit current conductor 1s: 0.9 kA
  • Voltage Drop: 6.8 V/A.km

 

Description

Description

Standards

  • National
    BS 6387 CWZ; BS 7846; BS 8519 cat. 3

Application:

Designed for use in large complex buildings like stadiums, airports, hospitals, hi-rise offices and residential buildings, fully meets requirements to maintain circuit integrity even through the most extreme fire conditions.

Built to release low levels of toxic fumes when burning, for use with fire safety engineering systems such as:

• fire alarm systems

• emergency lighting

• other systems which help to ensure the safest evacuation and assist in the firefighting stages of a fire.

 

Construction:

  1. Conductor: Copper
  2. Fire barrier: Mica tape
  3. Insulation: XLPE
  4. Inner layer: Glass-fiber tape
  5. Bedding: LSZH
  6. Armour: Single layer of galvanized steel wires
  7. Outer layer: Glass-fiber tape
  8. Outer sheath: LSZH

 

NX600 cables should meet the F2 & F120 requirements of BS 6387 &  BS 8491 at 120 minutes for cables diameter over 20 mm

          • Resistance to fire, with mechanical shock and water jet

          • Additionally meeting the BS 8519 category 3 requirements

Marking:

ELECTRIC CABLE  600/1000 V  BS 7846-F120  NEXANS i  NX600  Number of cores x cross section  LPCB 946d/01  BASEC  ''YEAR'' 

 

 

Main certifications

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Armour type
Single layer of galvanized steel wires
Outer sheath
LSZH
Insulation
XLPE + Mica tape
Sheath colour
Black
Conductor flexibility
Class 2
Halogen free
Yes
Type of conductor
Circular, stranded, class 2

Dimensional characteristics

Dimensional characteristics

Average insulation thickness
- mm
Conductor diameter
- mm
Inner sheath thickness
- mm
Nominal outer sheath thickness
- mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Operating temperature, range
-20 ... 60 °C
Max. conductor temperature in service
90 °C
Fire resistant
BS 8491 - 120 min
Smoke density
IEC 61034-1-2
Gases corrosivity
IEC 60754-2
Flame retardant
IEC 60332-3-24
Bending factor when laying
8 (xD)
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close